![]() |
City of Charlottesville, VA Fire
Department
|
Chapter: | III - Equipment Operations |
Subject: | Preventive Maintenance - S.C.B.A.'s |
Code: | 2-III-8 |
Revised: | 3-10-94 |
To establish those guidelines necessary for compliance with OSHA and manufacturers recommendations for maintenance standards of self-contained breathing apparatus (S.C.B.A.).
A. Only those individuals who have been trained and certified by the equipment manufacturer may perform the maintenance procedures on department owned self-contained breathing apparatus.
B. Replacement or repairs shall be done only by qualified persons, using parts or supplies designed for the breathing apparatus. No attempt shall be made to make adjustments beyond manufacturers recommendations. Parts shall not be interchanged among devices of different manufacturers.
C. All maintenance procedures and time schedules shall conform to OSHA, NFPA, and manufacturers recommendations and guidelines.
D. All breathing apparatus maintenance shall be performed in the air mask service area, so designated by the department.
1. The rear portion of the Fire Equipment Mechanics Office shall be the only authorized S.C.B.A. repair and service area.
E. Tools that have been painted blue are designated as breathing apparatus maintenance tools and can only be used for the repair, adjustment and service of self-contained breathing apparatus or the respiratory air compressor system.
The Fire Equipment Mechanic and/or those department personnel so assigned shall be the only individuals who may perform maintenance on department owned SCBA's except for the routine cleaning of the SCBA.
All department owned S.C.B.A. shall undergo the inspection, cleaning and maintenance procedures outlined in this policy.
A. Daily inspection and operational check; the following steps will be performed on all SCBA on a daily basis:
1. Cylinder pressure will be between 2000 and 2200 psi or cylinder must be recharged or replaced.
2. Examine facepiece and breathing tube assembly for cleanliness, broken or deteriorating parts and proper exhalation valve operation. Personnel will check facepiece for proper facial seal by placing face piece against the face, cupping hand on breathing tube end and inhaling. Gently exhale to check proper exhalation valve operation.
3. Each individual shall sanitize the facepiece assigned for his/her use with M.S.A. cleaner/ sanitizer (see 2-III-7).
4. Harness straps shall be inspected for excessive wear, loose screws and proper operation of the strap adjustment hardware. The tank should not be loose in the frame.
5. The operation check will be performed in the following sequence:
a. check regulator valves; the main line valve should be fully open, the bypass valve should be fully closed.
b. check high pressure hose handwheel for tightness.
c. check to be sure the regulator outlet port is covered with the rubber dust cover.
d. with your hand over the outlet cover, pressurize the regulator by turning the tank valve handwheel counter-clockwise.
e. listen for the alarm bell to ring as the pressure builds but the bell should quit ringing as the pressure builds above 1200 psi on the regulator gauge.
f. remove hand from outlet cover, the cover should remain in place.
g. check to verify that the regulator gauge and tank gauge are equal (and 50 psi). '
h. turn off the tank valve and watch the regulator gauge for 30-45 seconds. There should be no noticeable drop in pressure.
i. lift an edge of the rubber outlet cover and slowly allow the air pressure to drop. When the alarm bell starts ringing, reseal the outlet cover and allow the alarm to ring until all air pressure is exhausted. The alarm should start to ring at 550 psi (and 50) and continue to ring until 200 psi or lower.
j. carrying cases for scba will be cleaned and the interior wiped with a damp rag or sponge.
k. breathing apparatus that does not perform properly as outlined must be returned to the maintenance division for repair (see 2-III-7).
B. After each use:
1. Air cylinder shall be recharged (see 2-III-9).
2. Harness assembly will be washed with mild soap and water and scrubbed with a soft bristle brush if necessary.
3. Never apply water to SCBA unless high pressure line is connected to an air cylinder and the regulator outlet port is covered.
4. Wash and sanitize face piece (see 2-III-7).
5. Perform daily inspection and operational check as outlined in 8.04-A.
C. The monthly inspection will be scheduled and conducted by the Fire Equipment Mechanic and/or those other individuals designated by the department. The monthly inspection program contains four (4) sections: flow testing, leak testing, visual inspection and if necessary, maintenance and repair of worn or damaged parts.
1. Regulators will be flow tested and test results recorded. Flow tests will be conducted using the portable regulator tester and procedures as outlined in the accompanying manual.
2. The regulator, high pressure hose, alarm, cylinder valve, and admission valve will be tested for leakage as outlined in the M.S.A publication "Testing and Repair Procedures Section 2."
3. A visual inspection of the entire apparatus shall be made as described in M.S.A. Publication "Testing and Repair Procedures Section 3." Areas to be covered include:
a. regulator diaphragm b. lever assembly c. pressure gauge d. high pressure hose e. air cylinder and valve f. facepiece g. breathing tube h. harness assembly
4. When all tests have been completed any repairs needed can be made before returning the apparatus to service.
5. Maintenance records for each S.C.B.A. shall be maintained and shall reflect findings of inspections and repairs made to breathing apparatus.
Go BACK to Book Two Contents page.
For Help using this system, send e-mail to: